A commissioning day

A 132 kV bay, a new RTU, and a SCADA master that will not accept a single indication. This is what a commissioning day can actually look like. We follow the signals all the way.

The bay is energised at ten past seven and nothing works. The RTU has power, the SCADA master is polling, and the operator three hundred kilometres away sees an empty list where twelve indications should be. Nobody in the control building can say whether the problem is the RTU, the cabling, the protocol configuration, or the master. That is the ordinary state of a commissioning morning, and it is exactly why a protocol analyzer is valuable on site.

The instinct is to start changing settings. But that is almost always wrong. Every setting changed before the link is understood is one more variable to unwind later, and on a live bay the unwinding happens under time pressure with a customer waiting. The alternative is to look first: put a passive tap on the line and read what the two ends are actually saying to each other.

Tapping the link

A serial tap is a passive listener. It does not answer, does not poll, and does not appear on the bus as a device — which matters, because on a bay that is already energised you cannot introduce new equipment without consequences. SerialMon is connected to the tap and decodes both directions at once.

RTU RS-485 TAP SCADA SERIALMON passive NTP
Figure 1. The RTU and the SCADA master share one RS-485 line. SerialMon listens through a serial tap and keeps its clock synchronized over NTP.

Within ninety seconds the picture is different. The master is polling. The RTU is answering. Frames are moving in both directions and the checksums are good — so the cable, the wiring and the baud rate are all fine, and three of the four candidate causes are gone before anyone has touched a configuration screen.

The link was never broken. It was answering a question nobody had asked it. Substation commissioning

Reading the telegrams

Raw bytes alone would not have settled it. 68 0E 0E 68 is a frame header and nothing more; what matters is the ASDU inside it, the cause of transmission, and the information object address. Seeing the parsed telegram beside the raw bytes — same row, same instant — is what turns a byte stream into an answer.

Shows raw and parsed data
Figure 2. SerialMon gives you the raw telegrams as well as parsed telegrams presented in an understandable way.

The RTU was sending its indications with a common address of one. The master was configured to expect two. Every telegram was well-formed, correctly framed, and quietly discarded at the far end. No error was raised anywhere, because from each end's point of view nothing had gone wrong.

Where the day went

07:10 Bay energised. Master polling, indication list empty at the control centre.
07:40 Serial tap fitted on the RTU line. Passive capture started, nothing on site changed.
07:42 Traffic in both directions, checksums good. Cable, wiring and baud rate ruled out.
08:05 Parsed telegrams show common address 1 from the RTU; the master expects 2.
08:30 RTU reconfigured. Indications appear at the control centre on the next General Interrogation.
09:00 Signal list imported. Point-by-point verification begins.
15:20 Last double-point indication accepted. Every signal in the list marked as tested.
15:45 FAT/SAT documentation exported from the tracking window and signed before leaving site.

Twenty minutes of listening replaced what would otherwise have been a morning of guessing, and the rest of the day went where it was supposed to go: proving every point in the signal list, one at a time, with a record of each result.

Address tracker IEC 60870-5-104
Figure 3. SerialMon keeps track of all signals. Load your own signal lists.

The same tool, on your next bay

SerialMon decodes nine telecontrol protocols over serial and TCP/IP, simulates master or slave roles per connection, and exports FAT/SAT documentation straight from the tracking window.